News and Information |
|
NEW ARRIVALS
|
|
Stabimatic Company Ltd UK |
|
PLATINUM SERIES(THREE PHASE) |
 |
|
|
|
GLT Platinum Series Three Phase Servo Type
(6KVA ~ 50KVA & 60 KVA ~ 1000KVA)
Key Features |
 |
Stabimatic Automatic Voltage Regulators are used for regulation against three phase line voltage fluctuations. In contrast to magnetic voltage stabilizers, this type is a real automatic voltage regulator with servo-motor control, applicable to low or high output power. One important feature is the overload capacity which may run to a multiple of the rated value for a short period of time without causing output voltage breakdown. Further advantages are the independence of load power factor, a small phase displacement and very high power efficiency. These regulators are used for three-phase applications and also for single phase.
The circuit configuration of a three phase regulator consists of ring-core variable transformer with servo-motor, three auxiliary transformer and three-points regulating unit. The three DC servo-motor is controlled by the regulating unit and connected to the ring-core variable transformer via a gear.
The position of a carbon brush on the variable transformer is set by the servo-motor.
Dependent of its position, the auxiliary transformer primary winding is supplied with a voltage in phase with or dephased to the line voltage. Thereby, line over voltage and under voltage is compensated.
Because of small dimensions and low weight, installation of this regulator is very easy and rapid. |
MODELS |
GLT 3KVA |
GLT 6KVA |
GLT I0KVA |
GLT 15KVA |
GLT 20KVA |
GLT 24KVA |
GLT30KVA |
GLT 40KVA |
GLT 50KVA |
GLT 75KVA |
GLT 100KVA |
GLT 150KVA |
GLT 200KVA |
GLT 250KVA |
GLT 300KVA |
GLT 500KVA |
GLT 600KVA |
GLT 800KVA |
GLT 1000KVA |
|
SPECIFICATIONS |
Input Voltage |
Three-phase and four wire 150-250 / 260-450 |
Output Voltage |
220/380 +0 to 1%
can be used single-phase and three phase |
Frequency |
50Hz/60Hz |
Response Time |
Within 0.3 sec. against 13% input voltage deviation |
Efficiency |
Better than 90% |
Ambient Temperature |
-5 C + 40 C |
Relative Humidity |
Less than 90% |
Waveform Distortion |
Additional waveform distortion of output voltage < 196 No waveform distortion |
Insulation Resistance |
More than 5Mw |
APPLICATIONS
Computers, Photocopy Machines, Telefax, Medical Test & Quality Control Equipments, Security & Communication Equipments, TV, VCR, Radar Station & Telephone Exchange, Cash Register Machine, Measuring Devices, Computerised Embroidery Machine and other costly electrical & electronic gadgets. |
|
|
|